ATV320U40N4WS | Schneider Electric 4kW IP65 VFD
VFD
- Brand: Schneider Electric
- Part Number:
ATV320U40N4WS - Availability: Ask for quote
Schneider Electric ATV320U40N4WS: 4 kW IP65 wall-mount VFD with disconnect, integrated EMC filter, Modbus/CANopen, and SIL3 safety. A reliable choice for demanding applications.
Product Details
Product Overview
The Schneider Electric ATV320U40N4WS is a 4 kW (5 HP) three-phase variable speed drive from the Altivar Machine ATV320 series, designed for wall mounting in demanding environments. Its IP65 enclosure with integrated disconnect switch and category C2 EMC filter makes it a reliable choice for applications requiring protection against dust and water jets. As a genuine Schneider Electric part, it delivers the performance and durability expected from a leading automation brand. At Mronexus, we offer this drive at competitive prices with fast delivery from stock, ensuring you get the right part quickly.

Key Technical Specifications
- Motor power: 4 kW (5 HP) at 380…500 V three-phase supply.
- Supply voltage: 380…500 V three-phase (-15%/+10%), 50/60 Hz.
- Nominal output current: 9.5 A at 4 kHz switching frequency.
- Operating temperature: -10 to +50 °C without derating; up to 60 °C with derating.
- Communication: Built-in CANopen and Modbus Serial line via RJ45; optional modules for Modbus TCP/EtherNet/IP, PROFINET, EtherCAT, and more.
- Safety: STO up to SIL3/PLe, plus SS1, SLS, SMS, GDL.
- Protection rating: IP65.
- Dimensions (H×W×D): 340 x 250 x 235 mm; weight 8.2 kg.
The integrated EMC filter (category C2) reduces electromagnetic interference, simplifying compliance with EN/IEC 61800-3. The drive supports both asynchronous and synchronous PM motors, with advanced control modes including flux vector control without sensor for precise speed and torque regulation.
Applications and Use Cases
The ATV320U40N4WS excels in applications where reliability and environmental protection are critical. Its IP65 rating allows installation in washdown areas, outdoor enclosures, or dusty environments without additional cabinets. Common uses include conveyor systems, material handling, packaging machines, and pumps. The integrated disconnect switch enables safe isolation during maintenance, while the category C2 EMC filter ensures compatibility with sensitive equipment. For a recent project, a food processing plant utilized this drive to control a 4 kW conveyor motor in a high-humidity zone, benefiting from the IP65 protection and fast delivery from Mronexus.

Installation and Setup
Mount the drive vertically (±10°) on a wall or machine frame, maintaining a minimum clearance of 100 mm around the unit for adequate airflow. Use wire cross-sections of 2.5 to 6 mm² and tighten terminals to 1.4 N·m. The supply voltage must be within 380…500 V three-phase; ensure the upstream protection device does not exceed 5 kA prospective short-circuit current. For motor connections, use shielded cables to maximize EMC performance, especially with the integrated filter. The drive is factory-set to 4 kHz switching frequency; higher frequencies require power derating. Refer to the installation manual NVE41289 for detailed wiring diagrams and safety instructions.
Compatibility and Integration
The ATV320U40N4WS integrates seamlessly into industrial networks. Built-in protocols include CANopen and Modbus Serial line, making it easy to connect to PLCs and HMIs. For Ethernet-based systems, optional communication modules support Modbus TCP/EtherNet/IP, PROFINET, EtherCAT, POWERLINK, and DeviceNet. When integrating into a fieldbus network such as PROFINET or EtherNet/IP, an external gateway or connection module may be required; confirm cable and gateway compatibility with Mronexus. The drive also supports a wide range of I/O: 3 analog inputs, 6 digital inputs, 1 analog output, 2 relay outputs, and a pulse output. This flexibility allows direct connection of sensors, encoders, and actuators without additional hardware.
Maintenance and Reliability
Regular maintenance ensures long service life. Inspect the drive every 6 to 12 months for dust accumulation, especially in IP65 installations where heat dissipation relies on the enclosure surface. Clean the cooling fins with dry compressed air. Check terminal tightness and motor cable condition. The operating temperature range of -10 to +50 °C without derating means the drive can handle most industrial environments, but avoid condensation and ensure humidity remains below 95% non-condensing. The integrated EMC filter and IP65 rating reduce the need for external protection, lowering total cost of ownership. For high-altitude installations above 1000 m, derate output current by 1% per additional 100 m up to 3000 m.
Troubleshooting Common Issues
If the drive trips on overcurrent, check motor cable length (max 10 m shielded with integrated filter) and verify motor parameters. Overheating alarms often indicate blocked ventilation or ambient temperature above 50 °C; clean the drive and improve airflow. Communication errors may arise from incorrect protocol settings or wiring; verify the RJ45 connection and termination. For persistent faults, consult the diagnostic codes in the programming manual. Many issues can be resolved by ensuring proper grounding and shielding. If you need replacement parts or technical guidance, contact Mronexus for genuine industrial automation parts.
Product Support and Availability
The ATV320U40N4WS is in stock and ready to ship from Mronexus. As your one-stop sourcing base for PLC, HMI, servo, sensor, and circuit breaker needs, we provide genuine parts at competitive prices with worldwide fast delivery. Contact Mronexus for genuine industrial automation parts and experience reliable, value-for-money service.
Frequently Asked Questions
Q: What is the operating temperature range of the ATV320U40N4WS?
A: The drive operates from -10 to +50 °C without derating. Above 50 °C, derating is required up to 60 °C per the catalog derating curve. Ensure adequate ventilation and respect the 100 mm clearance around the unit.
Q: Can the ATV320U40N4WS be integrated into an Ethernet network?
A: Yes, via an optional communication module. The drive has a slot for Modbus TCP/EtherNet/IP, PROFINET, EtherCAT, and other protocols. Built-in ports include CANopen and Modbus Serial line on RJ45. For fieldbus networks, an external gateway may be required; confirm compatibility with Mronexus.
Q: What is the maximum motor cable length with the integrated EMC filter?
A: With the integrated category C2 EMC filter, maximum shielded motor cable length is 10 m at 4 kHz switching frequency. For longer cables, consider an external filter or consult the installation manual.
Q: Does the ATV320U40N4WS support safety functions?
A: Yes, it includes a STO input and four configurable safety inputs, supporting STO up to SIL3/PLe, SS1, SLS, SMS, and GDL per IEC 61800-5-2 and IEC 61508.
Unmatched Customer Service
- After Hours Shipping
- Real Time Order Tracking
- Flexible Delivery Options
- Intact Technical Supports