MTL3013 | MTL 2-Ch Switch/Proximity Detector Relay
HMI
- Brand: MTL
- Part Number:
MTL3013 - Availability: Ask for quote
MTL3013 two-channel switch/proximity detector relay enables independent control of two safe-area loads from hazardous-area sensors. 10ms response, 250V 5A contacts.
Product Details
When a Single Changeover Switch Must Control Two Independent Loads
A chemical plant needed to monitor two redundant level switches in a Zone 0 tank while keeping safe-area alarms fully isolated. The existing single-channel relays required twice the panel space and complicated wiring. The MTL3013 solves this by packing two interconnected, fully floating channels into one compact unit. Each channel can be controlled independently by proximity detectors or switches in hazardous areas, or both can be driven by a single changeover switch. This dual-channel design reduces installation cost and panel footprint without compromising safety or reliability.

Key Features and Technical Specifications
- Two interconnected, fully floating channels – each channel operates independently for maximum flexibility.
- Voltage applied to sensor: 7.0 to 8.5V dc from 970Ω, compatible with NAMUR and DIN19234 proximity detectors.
- Input/output characteristics: Output closed if >2.1mA (<2kΩ); output open if <1.2mA (>10kΩ); hysteresis 200µA (650Ω) typical.
- Phase reverse facility: Top-mounted switches reverse operation, allowing alarm signalling for either sensor state.
- Relay contact rating: 250V 5A 100VA (ac) or 250V 5A 100W (dc) per channel.
- Response time: 10ms typical, ensuring fast reaction to sensor changes.
- Contact life expectancy: 1.5 x 105 operations at maximum load; >106 operations at 200V ac peak or dc, 10VA (resistive load).
- Power requirement: 55mA typical at 24V; 75mA maximum at 20 to 35V.
- Power dissipation: 1.4W typical at 24V; 1.6W maximum at 35V.
- Safety description (each channel): 10.5V, 800Ω, 14mA, Um = 250V rms or dc; FM max entity parameters: Voc = 10.5V, Isc = 14mA, Ca = 2.4µF, La = 165mH.
- LED indicators: Each channel has an LED that is ON when the output circuit is closed.
- Replaceable fuse: 80mA, 5 x 20mm glass to DIN41571 sheet 2, semi-time-lag (M).
- Weight: 170g.
The MTL3013 excels in applications requiring reliable isolation and fast response. Its 10ms response time and robust relay contacts make it ideal for emergency shutdown and alarm systems. The phase reversal feature adds diagnostic flexibility without additional hardware.
Applications and Use Cases
The MTL3013 is designed for hazardous-area signal interfacing. Typical applications include:
- Level monitoring in Zone 0 tanks using two redundant proximity detectors.
- Emergency shutdown systems where a single changeover switch must trip two independent safe-area loads.
- Alarm annunciation from hazardous-area switches, with phase reversal for fail-safe configuration.
- Pump control in Div 1 locations, using two channels for run and fault indication.
In a typical installation, two proximity detectors in a hazardous area connect to the MTL3013, which then controls two safe-area relays. This provides galvanic isolation and ensures that a fault in one channel does not affect the other.

Installation and Setup
The MTL3013 is designed for panel mounting. Connect the hazardous-area sensors to the input terminals, observing polarity for NAMUR devices. The output relay contacts are accessible via a separate terminal block. Use the top-mounted phase reversal switches to set the desired alarm state. Ensure that the 24V dc power supply is within the 20–35V range and that the replaceable fuse is intact. For reactive loads, install appropriate suppression to avoid contact arcing.
Maintenance and Reliability
Regular inspection of the MTL3013 is recommended as part of any preventive maintenance schedule. Check the LED indicators for proper operation and verify that the relay contacts are not sticking. The replaceable fuse protects the unit from overcurrent; if it blows, investigate the cause before replacement. The relay contacts are rated for 1.5 x 105 operations at maximum load, but reactive loads must be adequately suppressed to achieve this life. In harsh environments, ensure the enclosure is protected from dust and moisture. The MTL3013’s robust design and high contact life make it a reliable choice for critical applications, reducing downtime and maintenance costs.
Compatibility and Integration
The MTL3013 is compatible with NAMUR and DIN19234 proximity detectors and switches. It can be integrated into existing control systems via its relay contacts. For network integration, such as PROFINET or EtherNet/IP, an external gateway or connection module may be required. Consult Mronexus for assistance with cables and gateways to ensure seamless integration.
Frequently Asked Questions
Q: What is the response time of the MTL3013 relay?
A: The MTL3013 has a typical response time of 10ms, ensuring fast switching for time-critical safety applications.
Q: Can the MTL3013 be used in Zone 0 hazardous areas?
A: Yes, the switch or proximity detector can be located in Zone 0, IIC, T6 hazardous areas (Div 1, Group A) when suitably certified. The safe-area relays are isolated.
Q: What is the contact rating of the MTL3013?
A: Each relay channel has a contact rating of 250V 5A 100VA (ac) or 250V 5A 100W (dc). Reactive loads must be adequately suppressed.
Q: Does the MTL3013 provide line-fault detection?
A: No, the MTL3013 does not include line-fault detection. For that feature, use MTL3011 or MTL3014 units instead.