Skip to content
sales@mronexus.com +86 180 3000 5825 Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China Reply within 24 hours Worldwide shipping

22A-D8P7F104 | Allen-Bradley PowerFlex 4 AC Drive 3.7kW

PLC

  • Brand: Allen-Bradley
  • Part Number: 22A-D8P7F104
  • Availability: Ask for quote

Allen-Bradley 22A-D8P7F104 PowerFlex 4 AC drive: 3.7kW, 380-480V, flange mount, RS-485. Genuine parts at competitive prices from Mronexus.

Product Details

Product Introduction: Allen-Bradley PowerFlex 4 AC Drive

The Allen-Bradley 22A-D8P7F104 is a PowerFlex 4 series adjustable-frequency AC drive designed for reliable motor control in industrial applications. With a 3.7 kW (5 HP) power rating and 380…480V AC 3-phase input, this flange-mount drive delivers 8.7 A continuous output current. Its built-in RS-485 DSI port supports Modbus RTU communication, enabling integration into automation networks. As a genuine Allen-Bradley product, it offers dependable performance for engineers seeking value-for-money solutions. Mronexus supplies this drive from stock, ensuring fast delivery worldwide.

Figure 1: Front view of the Allen-Bradley 22A-D8P7F104 industrial automation component showing its physical design and enclosure.

Key Features & Technical Specifications

  • Input Voltage: 380…480V AC, 3-phase, ±10% tolerance (340…528V AC range).
  • Output Power: 3.7 kW (5 HP) with 8.7 A continuous output current.
  • Operating Temperature: -10…+50 °C for IP20/Open Type; -10…+40 °C with IP30/NEMA 1 kit.
  • Communication Protocol: Built-in RS-485 DSI port supporting Modbus RTU (function codes 03, 06, 16).
  • Power Supply: 380…480V AC 3-phase input, 50/60 Hz, 8.6 kVA at 9.0 A input current.
  • Control Method: PWM output with programmable carrier frequency (2…16 kHz, default 4 kHz).
  • Overload Capacity: 150% for 60 s, 200% for 3 s (I2t motor protection).
  • Efficiency: 97.5% typical, reducing energy losses.
  • Enclosure: Flange Mount, IP20 / NEMA/UL Type Open; IP30 kit available separately.
  • Braking: Integral brake IGBT; external brake resistor required (min. 97 Ω).

The drive’s convection cooling in flange-mount configuration eliminates fan maintenance, enhancing reliability in dusty environments. The 100 ms power ride-through ensures stable operation during brief voltage dips.

Applications & Use Cases

The 22A-D8P7F104 suits a variety of industrial motor control tasks. In conveyor systems, its 150% overload capacity handles startup loads, while the RS-485 port allows networked speed control. For HVAC fans and pumps, the drive’s 97.5% efficiency and programmable accel/decel times (0…600 s) reduce energy consumption and mechanical stress. Material handling equipment benefits from the flange-mount design, which dissipates heat outside the enclosure, and the IP30 option provides protection in dusty areas. In packaging machinery, the built-in keypad and LED display enable quick parameter adjustments without external tools. The drive’s Modbus RTU capability supports integration with PLCs and HMIs, making it a versatile choice for retrofits and new installations.

Figure 2: Technical layout and connection details for the Allen-Bradley 22A-D8P7F104 industrial automation component.

Installation & Setup

Mount the drive vertically on a panel using the flange-mount configuration, ensuring adequate clearance for airflow. Connect 380…480V AC 3-phase power to terminals L1, L2, L3, and motor leads to T1, T2, T3. Use shielded motor cables to minimize EMI; maximum cable length is 10 m without external filters (100 m with L-type filter). The RS-485 DSI port uses a 2-position terminal block (AK-U0-RJ45-TB2P) for Modbus wiring. Set node address (A104) and baud rate (A103) via parameters. For CE compliance, install an external EMC filter (22-RF012-BS or -BL). Refer to the official datasheet for detailed wiring diagrams and torque specifications.

Maintenance & Reliability

Regular inspection every 6 months is recommended: check heatsink for dust accumulation, verify terminal tightness, and inspect cooling paths. The convection-cooled flange-mount design has no cooling fan, reducing wear points. Operating temperature range (-10…+50 °C) and 0…95% non-condensing humidity ensure reliability in challenging environments. The drive’s 100 ms power ride-through and 0.5 s logic ride-through prevent nuisance trips during short power interruptions. With 97.5% efficiency, internal heat generation is minimized, extending component life. For preventive maintenance, monitor DC bus voltage (overvoltage trip at 810 V DC, undervoltage at 390 V DC) and output current via parameters. These features contribute to low total cost of ownership.

Compatibility & Integration

The 22A-D8P7F104 integrates with Allen-Bradley PLCs and HMIs via its RS-485 DSI port using Modbus RTU. For EtherNet/IP or DeviceNet networks, external communication kits (22-XCOMM-DC-BASE with 22-COMM-E or 22-COMM-D) are available. The drive supports up to two peripherals, such as remote keypads (22-HIM-C2) or communication adapters. Integration Note: When wiring into fieldbus networks like PROFINET or EtherNet/IP, an external gateway or connection module may be required; confirm cable and gateway compatibility with Mronexus. The drive’s analog input (0…10V or 4…20 mA) and 5 digital inputs (3 dedicated, 2 programmable) interface with sensors and switches. A programmable Form C relay output enables fault signaling or run indication.

Product Support & Availability

The 22A-D8P7F104 is in stock and ready to ship from Mronexus. As your one-stop sourcing base for industrial automation parts, we offer genuine Allen-Bradley drives at competitive prices. Contact Mronexus for genuine industrial automation parts and fast delivery worldwide.

Frequently Asked Questions

Q: What is the operating temperature range for the 22A-D8P7F104?

A: The drive operates from -10 to +50 °C in IP20/Open Type configuration. With the optional IP30/NEMA 1 kit, the range narrows to -10 to +40 °C. Flange-mount versions allow the heatsink at -10 to +40 °C while the drive body remains -10 to +50 °C.

Q: Can the 22A-D8P7F104 be connected to a Modbus RTU network?

A: Yes, the built-in RS-485 DSI port supports Modbus RTU with function codes 03, 06, and 16. Node addresses range from 1 to 247, and baud rates from 1200 to 38400 bit/s (default 9600). For networks exceeding 32 nodes, RS-485 repeaters may be required.

Q: What input voltage does the 22A-D8P7F104 require?

A: The drive accepts 380…480V AC, 3-phase input with ±10% tolerance, corresponding to an input voltage range of 340…528V AC. Input frequency is 50/60 Hz. The rated input current is 9.0 A with a branch fuse of 15 A.

Q: Does the 22A-D8P7F104 include an EMC filter?

A: No, this catalog number has no integral EMC filter. For CE compliance, an external filter is required—either the S Type 22-RF012-BS or L Type 22-RF012-BL. Refer to the official datasheet for filter selection and cable length limitations.

Unmatched Customer Service

  • After Hours Shipping
  • Real Time Order Tracking
  • Flexible Delivery Options
  • Intact Technical Supports

Latest News

Insights, product guides and industry updates from our team.

Need a quote or technical support?

Send us your part numbers and we will get back within 24 hours.

Contact Us