Skip to content
sales@mronexus.com +86 180 3000 5825 Room 7A, No. 59 Hubin North Road, Siming District Xiamen City China Reply within 24 hours Worldwide shipping

IC670MDL330 | GE 16-Point AC Output Module, 12-120VAC

Servo Motor

  • Brand: GE
  • Part Number: IC670MDL330
  • Availability: Ask for quote

The GE IC670MDL330 is a 16-point discrete AC output module for Field Control systems. It delivers 12-120VAC at 1A per point with 1500VAC isolation, ensuring reliable control of solenoids, relays, and pilot lamps.

Product Details

IC670MDL330: Solving AC Output Challenges in Field Control Systems

Industrial engineers often face the challenge of reliably switching AC loads in distributed I/O architectures. The GE Fanuc IC670MDL330 discrete output module addresses this by providing 16 sourcing output channels in a single group, each capable of delivering 1A at 12-120VAC. Part of the Field Control series, this module is designed for energizing solenoids, relay coils, pilot lamps, and other on/off devices. With built-in fuse protection and RC snubber circuits per output, it ensures dependable performance in demanding environments.

Figure 1: Front view of the GE IC670MDL330 industrial automation component showing its physical design and enclosure.

Key Features & Technical Specifications

The IC670MDL330 combines robust output capability with advanced protection features. Below are the critical specifications that make it a reliable choice for industrial automation:

  • Output Channels: 16 discrete outputs, single group, each with individual LED status indicator.
  • Output Voltage: Nominal 12-120VAC, operating range 10-132VAC, 47-63Hz.
  • Output Current: 1A per point, 4A per module maximum; minimum load 10mA per point.
  • Isolation: 1500VAC for 1 minute, 250VAC continuous (user to logic/frame ground).
  • Response Time: ½ cycle ON/OFF for fast switching.
  • Protection: Built-in 5A slow-blow fuse (5x20mm) per group, RC snubber per output.
  • Power Draw: 275mA maximum from Bus Interface Unit (BIU) power supply.
  • Inrush Current: 10A maximum per output for one cycle (20ms).
  • Output Voltage Drop: 2.0V maximum; leakage current <2mA at 120VAC.

The 1500VAC isolation is particularly critical in mixed-voltage environments, preventing ground loops and protecting sensitive logic circuitry from AC transients.

Applications & Use Cases

The IC670MDL330 excels in applications requiring reliable AC switching. In manufacturing lines, it controls solenoid valves and motor starters, ensuring precise timing. For building automation, it manages lighting contactors and HVAC dampers. In material handling, it drives diverters and gates. The module’s ½ cycle response time supports high-speed sorting, while the built-in fuse and snubber circuits reduce downtime by protecting against short circuits and inductive kickback. Whether you’re upgrading an existing Field Control system or building a new panel, this module delivers the performance needed for demanding industrial environments.

Figure 2: Technical layout and connection details for the GE IC670MDL330 industrial automation component.

Installation & Setup

Installing the IC670MDL330 is straightforward when following proper procedures. First, ensure the Bus Interface Unit (BIU) is powered down. Mount the module securely on the Field Control rail, making sure it seats correctly. Connect the output wiring to the terminal block, observing the voltage and current ratings. The module draws 275mA from the BIU power supply; verify the BIU can handle the total load. Use shielded cables for signal lines to minimize noise. After wiring, apply power and check the individual channel LEDs for proper operation. The fuse OK LED should be illuminated; if not, inspect the fuse. Always follow local electrical codes and the official GE installation manual for detailed instructions.

Maintenance & Reliability

To ensure long-term reliability, establish a routine maintenance schedule. Inspect the module every six months for signs of overheating, loose connections, or dust accumulation. The built-in fuse is replaceable; use a 5A slow-blow fuse (5x20mm) if blown. The RC snubber circuits require no maintenance but should be checked for physical damage. Operating temperature should remain within the specified range (refer to datasheet). In high-vibration environments, verify terminal tightness regularly. By following these practices, the IC670MDL330 can provide years of dependable service, reducing unplanned downtime and maintenance costs.

Compatibility & Integration

The IC670MDL330 is designed for use with GE Fanuc Field Control systems, specifically interfacing with a Bus Interface Unit (BIU). The BIU supplies logic power and communicates output data serially. The module loops back serial data for verification, ensuring data integrity. For integration into higher-level networks such as PROFINET or EtherNet/IP, an external gateway or connection module may be required. Always confirm cable and gateway compatibility with your supplier. The module’s 16-bit discrete output data is easily mapped into the control system’s memory.

Troubleshooting & Common Issues

Common issues include a blown fuse, indicated by the fuse OK LED being off. Replace with a 5A slow-blow fuse. If an output fails to energize, check the corresponding LED; if off, verify the output command from the BIU. If the LED is on but the load doesn’t operate, check wiring and load current (minimum 10mA). Excessive voltage drop may indicate a faulty snubber or overload. For communication errors, verify the BIU connection and serial data loopback. Always refer to the official GE documentation for detailed troubleshooting.

Product Support & Availability

Mronexus stocks the IC670MDL330 and other genuine GE Fanuc Field Control modules. We offer fast delivery from stock and worldwide shipping. As your one-stop sourcing base for industrial automation parts, we ensure you get reliable components at competitive prices. Contact Mronexus for genuine industrial automation parts.

Frequently Asked Questions

Q: What is the output voltage range of the IC670MDL330?

A: The nominal output voltage is 12-120VAC, with an operating range of 10-132VAC at 47-63Hz.

Q: How much current can each output channel handle?

A: Each point can handle 1A maximum, with a module total of 4A. Minimum load is 10mA per point.

Q: What type of fuse does the IC670MDL330 use?

A: It uses a 5A slow-blow fuse, 5x20mm, for group protection. The fuse is replaceable.

Q: Is the IC670MDL330 compatible with all Field Control BIUs?

A: Yes, it interfaces with any Field Control Bus Interface Unit. For network integration, an external gateway may be needed.

Q: What is the isolation rating?

A: 1500VAC for 1 minute and 250VAC continuous between user input and logic/frame ground.

Unmatched Customer Service

  • After Hours Shipping
  • Real Time Order Tracking
  • Flexible Delivery Options
  • Intact Technical Supports

Latest News

Insights, product guides and industry updates from our team.

Need a quote or technical support?

Send us your part numbers and we will get back within 24 hours.