IC694ALG442 | GE RX3i Analog I/O Module, 4 In/2 Out
PLC
- Brand: GE
- Part Number:
IC694ALG442 - Availability: Ask for quote
The IC694ALG442 is a GE RX3i analog combination module with 4 differential inputs and 2 single-ended outputs, configurable for voltage or current signals. 12-bit resolution, 24V DC supply, hot-swap support.
Product Details
The Evolution of Analog Control: Why the IC694ALG442 Still Matters
For decades, industrial automation has moved from relay-based logic to sophisticated programmable automation controllers. The GE Fanuc RX3i series, now under Emerson Automation, represents a mature platform that balances proven reliability with modern flexibility. The IC694ALG442 analog combination module is a testament to this evolution—a single module that handles both input and output signals, reducing footprint and wiring complexity. In an era where every panel inch counts, this integration is a quiet revolution. For engineers seeking genuine parts at competitive prices, this module delivers value without compromise.

Key Features & Technical Specifications
- Four differential analog input channels and two single-ended analog output channels.
- Configurable per channel: 0-10 VDC, -10 to +10 VDC, 0-20 mA, 4-20 mA, and 4-20 mA enhanced.
- 12-bit digital resolution for precise signal representation.
- Channel update rate of 2 ms; module update rate of 3 ms.
- Requires external 20-30 VDC power supply (24 VDC typical) with <10% ripple.
- Draws 95 mA from 5 VDC backplane and 150 mA from 24 VDC user supply.
- Supports hot-swap for online replacement without system shutdown.
- Configurable output states (Hold or downscale) on controller stop or power loss.
- Open-wire detection and alarm customization enhance diagnostics.
- Operating temperature range: 0 to 60°C (32 to 140°F) — refer to datasheet for full details.
The 12-bit resolution translates to a voltage resolution of 2.5 mV for 0-10 V inputs, enabling accurate monitoring of pressure or flow transmitters. The fast 2 ms update rate ensures responsive closed-loop control, critical in fast-moving processes.
Applications & Use Cases
This module excels in continuous process control where analog signals are the lifeblood of operation. In a water treatment plant, the four inputs can monitor pH, turbidity, chlorine, and flow, while the two outputs drive chemical dosing pumps. In a manufacturing line, it might interface with load cells and variable frequency drives, providing both measurement and command signals. The configurable output states are particularly valuable: on a power failure, the module can hold the last output value to maintain a valve position, or drive it to a safe downscale state, preventing dangerous overpressure. Such flexibility makes the IC694ALG442 a reliable choice for critical infrastructure.

Installation and Setup
Installation is straightforward in any vacant slot of an RX3i backplane, local or distributed. The module can also serve as distributed I/O for RX7i systems and Series 90-30 PLCs. Wiring should use shielded twisted-pair cables for analog signals, with shields grounded at the module end. The external 24 VDC supply must be clean, with ripple under 10%; a regulated power supply is recommended. Configuration is performed via GE Fanuc’s Machine Edition software, where each channel’s range and output state behavior are defined. Ensure the module’s IP20 rating is respected by mounting it in a protective enclosure, and provide adequate RF shielding in electrically noisy environments.
Maintenance and Reliability
With no moving parts, the IC694ALG442 is inherently reliable. Routine maintenance involves periodic inspection of terminal connections and verification of signal accuracy. In high-vibration areas, check terminal screws every six months. The module’s open-wire detection alerts operators to broken sensor loops, preventing undetected failures. Operating within the specified temperature range and protecting from moisture and dust will maximize service life. Because the module supports hot-swap, replacement can be done quickly, minimizing downtime and reducing maintenance costs.
Compatibility and Integration
The IC694ALG442 is compatible with RX3i PACSystems, RX7i (as distributed I/O), and Series 90-30 PLCs. It communicates via the backplane; no external communication protocol is required. For integration into fieldbus networks such as PROFINET or EtherNet/IP, an external gateway or connection module may be needed. Confirm cable and gateway compatibility with your supplier. The module’s configurable output states ensure safe integration with modulating devices, and the Machine Edition software simplifies configuration and commissioning.
FAQ
Q: What is the input voltage range of the IC694ALG442?
A: The module accepts 0-10 VDC unipolar, -10 to +10 VDC bipolar, 0-20 mA, 4-20 mA, and 4-20 mA enhanced signals on its four differential input channels.
Q: How many analog channels does the IC694ALG442 provide?
A: It has four differential analog input channels and two single-ended analog output channels, each individually configurable.
Q: What is the power supply requirement for the IC694ALG442?
A: The module requires an external 20-30 VDC supply (24 VDC typical) with less than 10% ripple. It also draws 95 mA from the backplane 5 VDC supply.
Q: Does the IC694ALG442 support hot-swap?
A: Yes, the module supports hot-swap, allowing replacement without powering down the RX3i system.
Product Support & Availability
The IC694ALG442 is in stock and ready to ship from Mronexus. As your one-stop sourcing base for industrial automation parts, we offer genuine GE modules at competitive prices with worldwide fast delivery. Contact Mronexus for genuine industrial automation parts.
Unmatched Customer Service
- After Hours Shipping
- Real Time Order Tracking
- Flexible Delivery Options
- Intact Technical Supports