The MTL ICC312 repeater power supply provides reliable 4-20mA signal isolation with dual outputs, line-fault detection, and 1500V isolation for demanding industrial applications.

Product Details

Reliable Signal Isolation for Critical 4-20mA Loops

In process control, a failed signal loop can halt production and compromise safety. The MTL ICC312 repeater power supply is engineered to prevent such failures by providing robust, isolated power and signal transfer for two-wire transmitters. As a maintenance engineer, you need instruments that not only perform but also simplify troubleshooting and reduce downtime. The ICC312 delivers exactly that: a dependable, DIN-rail mounted solution that isolates, repeats, and monitors 4-20mA signals with precision and built-in diagnostics.

This independently powered isolator supplies a fully isolated dc voltage to energise a two-wire transmitter while simultaneously transferring the transmitter current to two separate output circuits. Each output can drive loads up to 1kΩ, making it ideal for feeding multiple monitoring or control systems from a single transmitter. With 1500V dc/ac isolation between input, outputs, and power supply, the ICC312 protects your control system from ground loops and transient voltages, ensuring signal integrity in electrically noisy plant environments.

Figure 1: Front view of the MTL ICC312 industrial automation component showing its physical design and enclosure.

Key Features and Technical Specifications

  • Input: One 4-20mA channel, configurable for 2-wire transmitter supply (terminals 7 & 8) or current source (terminals 8 & 9).
  • Outputs: Two independent 4-20mA outputs, each capable of driving loads up to 1kΩ.
  • Isolation: 1500V dc/ac between input, output 1, output 2, and power supply, eliminating ground loops.
  • Power Supply: 20 to 35V dc; maximum current draw 150mA at 20V dc with a 20mA signal.
  • Transmitter Supply: Minimum 20V available at 20mA, ensuring compatibility with a wide range of 2-wire transmitters.
  • Transfer Accuracy: Better than 20μA at 25°C for both outputs, with temperature drift <1μA/°C.
  • Line-Fault Detection (LFD): Open-collector output turns OFF when input current <0.2mA (broken cable) and ON when >1mA, enabling alarm signalling.
  • Response Time: 80ms to reach 90% of span, 280ms to reach 99.9% of span.
  • Operating Temperature: -20°C to +55°C; storage -40°C to +80°C; humidity 5 to 95% RH non-condensing.
  • Mounting: Directly onto T- or G-section DIN-rail (DIN 46277); 40mm wide polyamide casing.

The line-fault detection feature is a standout for maintenance teams: it provides a clear, isolated alarm signal when a transmitter cable breaks, allowing rapid fault localisation without loop interruption.

Applications and Use Cases

The ICC312 is suited to a wide range of industrial automation scenarios where reliable signal isolation and duplication are essential. In chemical plants, it can isolate a pressure transmitter feeding both a DCS and a local indicator, preventing ground loops that would otherwise distort readings. In water treatment facilities, the dual outputs allow one flow signal to be sent to a PLC and a chart recorder simultaneously, while the LFD output alerts operators to sensor cable damage. For OEM machine builders, the compact DIN-rail design and wide temperature range make it a robust choice for panel integration. The ICC312 also excels in retrofit projects where existing transmitters need to feed modern control systems without replacing the sensor.

Figure 2: Technical layout and connection details for the MTL ICC312 industrial automation component.

Installation and Setup

Mounting the ICC312 is straightforward: clip it directly onto T- or G-section DIN-rail to DIN 46277. Terminals accommodate 2.5mm² conductors, and the 40mm width saves valuable panel space. Wiring is clearly marked: connect the 2-wire transmitter to terminals 7 and 8 (observing polarity), or a current source to terminals 8 and 9. The power supply (20-35V dc) connects to the dedicated terminals, and the two outputs are available on separate terminal pairs. For the LFD output, wire the open-collector transistor to your alarm circuit, ensuring the maximum voltage (26V dc) and current (50mA) are not exceeded. Always verify isolation between all circuits before powering up.

Maintenance and Reliability

From a maintenance perspective, the ICC312 is designed for long, trouble-free service. The polyamide casing is durable and resistant to typical industrial contaminants. There are no moving parts or user-serviceable components inside, so routine maintenance is limited to periodic visual inspection of terminals and wiring. Check terminal tightness annually and inspect for signs of corrosion or loose strands, especially in high-vibration areas. The operating temperature range of -20°C to +55°C covers most indoor installations; ensure adequate ventilation if mounted in sealed enclosures. The LFD feature itself acts as a continuous self-check: if the input cable breaks, the alarm output triggers, allowing prompt corrective action. With a common-mode rejection ratio of 150dB typical, the ICC312 maintains accuracy even in electrically noisy environments, reducing nuisance trips and extending service life.

Compatibility and Integration

The ICC312 integrates seamlessly with standard 4-20mA control systems, PLCs, and DCS I/O cards. Its 1500V isolation protects sensitive input cards from field transients. When wiring into a fieldbus network (e.g., PROFINET, EtherNet/IP), note that the ICC312 is an analogue isolator and does not communicate over the bus; integration into such networks may require an external gateway or connection module. Always confirm cable and gateway compatibility with your supplier. The ICC312 is also compatible with a wide range of 2-wire transmitters, provided the minimum 20V supply at 20mA is sufficient for the transmitter’s requirements.

Troubleshooting and Common Issues

If the output signal is absent or incorrect, first verify the power supply voltage at the ICC312 terminals (20-35V dc). Check the input wiring: for a 2-wire transmitter, ensure terminals 7 and 8 are used with correct polarity. If the LFD alarm is active, inspect the transmitter cable for breaks or loose connections. A current source connected to terminals 8 and 9 should have a maximum voltage drop of 2.4V; excessive drop may indicate a faulty source. If the output load exceeds 1kΩ, the signal may clip; reduce the load or use a signal conditioner. For persistent issues, refer to the official MTL documentation or contact Mronexus for genuine replacement parts.

Product Support and Availability

The MTL ICC312 is in stock and ready to ship from Mronexus, your one-stop sourcing base for genuine industrial automation parts. We offer fast delivery worldwide, ensuring you get the parts you need without delay. Contact Mronexus for genuine industrial automation parts and competitive pricing on the ICC312 and other MTL products.

Frequently Asked Questions

Q: What is the power supply requirement for the MTL ICC312?

A: The ICC312 requires a 20 to 35V dc power supply. It draws a maximum of 150mA at 20V dc when supplying a transmitter with a 20mA signal, and 120mA maximum at 35V dc under the same conditions.

Q: How does the line-fault detection feature work on the ICC312?

A: The line-fault detection (LFD) output is an open-collector transistor that turns OFF when input current falls below 0.2mA (indicating a broken cable) and turns ON when input current exceeds 1mA. This output can drive an alarm circuit, with a maximum permitted voltage of 26V dc and maximum ON current of 50mA.

Q: Can the ICC312 provide two independent outputs from one transmitter?

A: Yes, the ICC312 provides two separate isolated output channels from a single 4 to 20mA input. Each output can drive loads up to 1kΩ, and both outputs are isolated from the input and power supply by 1500V dc/ac.

Q: What is the operating temperature range for the MTL ICC312?

A: The ICC312 operates reliably in ambient temperatures from -20°C to +55°C. For storage, the range extends from -40°C to +80°C. Humidity tolerance is 5 to 95% RH, non-condensing.